Reducing noise from heat transfer plates within radiant
panels.
Fastener Finesse
 |
| Figure 2 |
|
Another installation detail that affects
expansion noise from tube-and-plate radiant panels is how staples, screws or
other fasteners are placed.
In an above-floor tube-and-plate system, you should only fasten the aluminum
plate on one side of the tube groove, as shown in Figure 1. This allows the
plate to open slightly as the tube is pressed in place. It also allows for
subsequent lateral movement of the plate as it is heated. A couple of
light-gauge staples are adequate to “tack” a 24-inch aluminum plate in place.
The final covering layer, be it nailed-down hardwood or a thin plywood cover
sheet, provides all the clamping force necessary to hold the tubing and plates
flat.
When plates are stapled up to the bottom of a subfloor, it’s important they
make good contact with that subfloor. I suggest a minimum of eight equally
spaced staples on each side of a 6-inch wide by 24-inch long aluminum plate to
ensure it’s tightly pressed against the subfloor. Any air gaps between the
plate and subfloor will decrease heat transfer.
In both above-floor and below-floor
installations, leave an expansion gap of at least 1/4 inch between the ends of
adjacent aluminum plates. This is more than sufficient to accommodate
lengthwise movement of the plates.
It’s a good practice to minimize situations where nails for hardwood flooring
are driven through heat transfer plates. By installing 6-inch-wide, single-tube
plates on 8-inch spacing, you create a 2-inch gap between plates, as shown in
Figure 2. This allows two nails to be located every 8 inches along the edge of
hardwood flooring without shooting nails through the plates. When using
14-inch-wide plates, it allows for two nails every 16 inches, as shown in
Figure 3.
Although either detail should provide plenty of nail-holding power for
well-dried wood flooring, my preference is for 6-inch plates at 8-inch spacing
because closer nail spacing generates less unusable short lengths of flooring.
 |
| Figure 3 |
|
It’s also important to remember that floors can
produce “squeaking” sounds due to shrinkage of the subfloor or wood sleepers.
This shrinkage creates slight gaps between the subfloor and underlying framing.
When someone steps on the floor over such a gap, the subfloor moves down, and
the shank of a nail in the vicinity may rub against the subfloor, resulting in
a squeak.
Many framers counter this by using a glued subfloor system. Construction
adhesive is placed at the top of the floor joists prior to fastening down the
subfloor. The fasteners then “clamp” the subfloor down while the adhesive sets.
The result is a tightly bonded subfloor/framing assembly with little
opportunity for differential movement and, thus, minimal potential for squeaks.
This detail is especially relevant for heated floors because elevated
temperatures accentuate wood shrinkage. Radiant panel installers should
recommend it to builders to avoid finger-pointing after the
fact.
It’s also prudent to use construction adhesive between sleepers and the
subfloor in an above-floor tube-and-plate system. Two light beads of
construction adhesive down the length of the sleeper should be sufficient. An
alternative is to apply adhesive to the backside of the sleepers using a
notched trowel, and immediately fasten it in place.
I also prefer the use
of plywood or OSB (oriented strand board) for the sleepers vs. solid sawn wood.
The latter is more prone to lateral shrinkage and cupping, especially if it’s
not well-dried.
Finally, in the case of radiant walls and
radiant ceilings, we’ve successfully used contact adhesive rather than mechanical
fasteners to secure aluminum heat transfer plates to strips of foil-faced
polyisocyanurate foam as shown in Figure 4. Again, 6-inch plates on 8-inch
centers provide a 2-inch-wide strip where drywall screws can be driven without
piercing the plates or coming close to the tubes.
When the assembly is done, the plates are clamped in place by surrounding
materials. The rubber compounds in the contact adhesive provide a slightly
elastic bond that can move with the plates without creating any noise. The
solvent-based contact adhesive we have used on several such systems is the same
adhesive used to bond laminate countertops, and can withstand temperatures up
to 200 degrees F, far higher than they will ever go in this type of
system.
One of the key benefits of a properly installed hydronic radiant panel system
is silent operation. Proper material selections — combined with control
techniques that gently steer temperatures up and down — can assure this is
achieved. Although Snap, Crackle, and Pop are great mascots for Kellogg’s Rice
Krispies, you don’t want them hanging out in your heating systems.
By: Chris Carlson
Posted: December 27, 2008 10:05 AM
Thank you,
Chris Carlson