Side-By-Side Vs. End-To-End
by John Siegenthaler, P.E.
December 1, 2008
The choice of piping
system can make a significant difference in operating cost.
If you’ve been reading my
PM
columns
over the last year, you’ve probably detected a penchant for reducing the power
used to circulate fluid through a hydronic distribution system. I see this as
“the final frontier” in the evolution of hydronic systems. Given that boilers
now yield thermal efficiencies in the mid- to upper-90 percent range (when
properly applied in low-temperature systems), the potential for further
reduction in system energy use must come from reduced electrical power
consumption.
There
are several factors that influence the total electrical power used by a
hydronic distribution system. These include the choice to zone with circulators
vs. electric zone valves vs. thermostatic radiator valves, choice of heat
emitters, circulator efficiency, operating temperature and choice of piping
layout.
This month, I want to discuss the latter in the
context of a simple residential system using fintube baseboard to supply a
50,000 Btu design heating load.
Lower Than You Thought?
I often ask audiences of
hydronic professionals at seminars to estimate the efficiency of a current
generation wet-rotor circulator in converting electrical energy to head energy.
Number guesses often range between 60 and 80 percent. Such numbers are probably
influenced by the relatively high thermal efficiencies of modern boilers.
It’s
always interesting to watch the reaction when the group learns that the
wire-to-water efficiency of current-generation wet-rotor circulators is
typically in the low 20-percent range, as can be seen on the red curve in
Figure 1. I was equally surprised when first informed about these wire-to-water
efficiencies.
Notice
that peak wire-to-water efficiency is achieved when the circulator operates
near the middle of its pump curve. If the piping system forces the circulator
to operate near the outer fringes of the pump curve, the corresponding wire-to-water
efficiency can approach single digits, as shown in Figure 2. Clearly, such
situations must be avoided.
Traditional Tactics
Consider the series-loop
baseboard system shown in Figure 3. It has been sized to provide 10,000 Btu/hr.
of heat output at each baseboard. Baseboard lengths increase in the downstream
direction to compensate for decreasing water temperature. The lengths have been
based on a flow rate of 5 gallons per minute, and a circuit supply temperature
of 180 degrees F. This produces a nominal 20-degree F temperature drop around
the circuit when it delivers 50,000 Btu/hr. The circuit is constructed of
3/4-inch, type M copper, with a total equivalent length (allowing for assumed
fittings) of 280 feet.
The
head loss of this circuit can be determined using tables, graphs or software.
For this example, I used the “Hydronics Design Studio” software to get an
estimated head loss of 13.2 feet. This corresponds to a pressure drop of 5.51
psi.
The
electrical wattage that must be supplied to a circulator to sustain a given
flow rate and corresponding circuit pressure drop can be calculated using
Formula 1.
Where: w e
= electrical wattage input to circulator (watts) f = flow rate
(gpm) ∆P = pressure drop of
circuit (psi) n = wire-to-water efficiency of circulator (decimal
percentage) 0.4344 = a unit conversion factor necessary for the stated
units
The
electrical wattage required for a circulator operating at the peak 22 percent
wire-to-water efficiency shown in Figure 1, and supplying the flow and
differential pressure requirements of this system, would be:
This number suggests a
small wet-rotor circulator operating on its medium or low speed setting can
provide the necessary hydraulic operating conditions.
Parallel Perks
Although fin-tube baseboard
is traditionally installed in series circuits using rigid copper tubing, this
is not the only act in town. Consider the homerun distribution system shown in
Figure 4. It consists of a manifold station and five homerun circuits of
1/2-inch PEX tubing, one to each baseboard. The equivalent length of each
homerun circuit is assumed to be 120 feet of 1/2-inch PEX tubing.
This
distribution system supplies the same water temperature to each baseboard.
Thus, to supply the 10,000 Btu/hr. load to each room, all baseboard lengths are
20 feet.
Analyzing
the hydraulic characteristics of this parallel system requires a bit more
mathematics than does a series loop, but such analysis is well within the scope
of the “Hydronics Design Studio” software. In this case, the homerun
distribution system, operating at 5 gpm, produces a head loss of 3.98 feet,
which corresponds to a circuit pressure drop of 1.68 psi.
Assuming a circulator with
the same 22 percent wire-to-water efficiency is used, the required electrical
power input to the circulator is:
This lower wattage is
directly attributable to the lower head loss of the parallel distribution
system in comparison to the traditional series circuit.
Although
the difference in operating power of these two systems seems small — 54.4-16.6
= 37.8 watts — it can have a significant effect on the operating cost of the
system over a design life of 20 years.
For
example: Assume both systems require the circulator to operate 3,000 hours per
year. Also assume a current cost for electricity of 14 cents/kwhr, and that
this cost inflates at 4 percent per year. Under this scenario, the series loop
would have an electrical operating cost $473 higher than that of the homerun
system over a period of 20 years.
The
calculations leading to this number are shown below.
This comparison assumes a
circulator of the required operating wattage can be located and used in either
system. This is not always the case, especially with fixed-speed circulators.
However, variable-speed ECM-based circulators with a wide range in input power
adjustment are becoming available in the United States. These products now
allow closer matching of circulator power with the requirements of the distribution
system.
In
general, parallel distribution systems such as the homerun system described
here will have lower head loss for the same rate of heat conveyance compared to
series circuits, or quasi-series circuits such as one-pipe systems using diverter
tees. Taking advantage of such systems is increasing important as the North
American hydronics industry strives to further reduce energy use without
sacrificing performance.
A watt
is a terrible thing to waste …
|