Ticked Off, Part 1
by John Siegenthaler, P.E.
October 7, 2008
Reducing noise from heat transfer plates within
radiant panels.
Imagine your family just moved into a new home
with radiant floor heating. During your first night, the heating system turns
on at 3 a.m. You don’t hear a thing because you’re sound asleep. However,
within a few minutes, the floors in several rooms start emitting “ticking”
sounds. These sounds repeat themselves and come from different areas of the
floor.
Eventually they get sufficiently frequent and loud enough to wake one of your
young children. Having no idea what’s causing the sound, your child panics,
thinking someone is trying to hack their way into the bedroom. Terrified, the
child runs from the room and jumps into bed with you. After some investigation,
you determine the sound is coming from the floor heating system, which consists
of PEX tubing and aluminum heat transfer plates.
Early the next morning, while you’re still “ticked off” over the situation, you
debate whether the first call should be to your real estate agent or your
attorney.
How would you like to be the heating contractor responsible for the above
installation?
I didn’t think so…
So how can you, as a hydronic heating professional, steer clear of a similar
situation?
Guaranteed Growth
The first step to avoiding it is understanding why
the noises are generated. They are caused by rapid temperature changes in
combination with materials having significantly different physical characteristics.
All materials expand when heated and contract when they cool. This certainly
includes PEX tubing and aluminum heat transfer plates. The amount of expansion
is determined by the initial length of the object, as well as a physical
property of the material called its coefficient of linear expansion.
The change in length due to change in temperature can be calculated using
Formula 1.
 |
| Formula 1 |
|
|
Where:
∆L = change in length due to temperature change (inch)
a = coefficient of linear expansion (inch/inch/degrees F)
L = original length (inch)
∆T = temperature change (degrees
F)
The coefficients of linear expansion for most materials are very small numbers.
Figure 1 gives some values for these coefficients relevant to the situation
being discussed:
 |
| Figure 1 |
|
|
Here’s how Formula 1 can be used along with the data
in Figure 1.
Assume a straight run of copper tubing that’s exactly 50 feet long when at an
initial temperature of 65 degrees F. The tube is wrapped in insulation. How
much does the tube’s length change when it’s filled with 200-degree F
water?
We’ll assume the insulated copper tube is very close to 200 degrees F when filled
with water at this temperature. The coefficient of linear expansion for copper
is 0.0000094 inch/inch/degrees F. Putting the numbers into Formula 1 yields:
Hence, the copper tube increased in length by a
little over 3/4 inches. That’s a significant change in length, especially if
the tube is rigidly clamped at its ends, or connected to elbows that pass
through holes in the floor. In the latter case, those holes need to have a
diameter that allows for the tube’s expansion without letting it press against
the side of holes. If this is not the case, the tube will be stressed, possibly
to the point of buckling.
It’s important to understand that a solid material does not emit any sound of
its own while expanding or contracting, provided the movement is not impeded by
surrounding materials or supports. It’s also important to realize that the
atomic level forces that cause thermal expansion are extremely powerful. They
cannot be “overpowered” by stronger fasteners or surrounding materials.
Instead, sufficient space must be provided to accommodate the expansion
movement. Not doing so can lead to high compressive stresses within the
materials.
Different Strokes
Next, let’s compare the difference in expansion
between a segment of PEX tubing and an aluminum heat transfer plate, both of
which are 24 inches long at 65 degrees F, and both of which rise to 140 degrees
F when operating in a radiant panel system.
The change in length of the aluminum plate is:
The change in length of the PEX tube is:
Although both numbers appear small, the
difference between them is what counts. In this case, the PEX tubing expands
about 0.146 inches more than the aluminum plate surrounding it. This differential
expansion is part of what causes the ticking sounds.
Another contributor is a phenomenon called “stiction,” which occurs between the
external EVOH oxygen diffusion barrier coatings on some PEX tubes and the
aluminum plates. Stiction is a situation in which the outer surface of the tube
weakly bonds to the aluminum plate. This allows compressive stress to build
within the tube wall as it warms up. At some point, the accumulating
compressive stress in the tube wall reaches the point where it breaks the loose
bond with the plate. The tube instantly moves a small amount along the plate; a
“tick” is the result.
This effect is enhanced by rapid temperature changes that occur when hot water
from the boiler races down a tube that’s been at room temperature for some
time. As if this weren’t enough, some ticking noise might be the result of
differential expansion between other materials in the floor including plywood,
rigid insulation or quasi-rigid floor coverings such as wood and tile. All
these materials have different coefficients of linear expansion and, thus, are
subject to differential expansion as the system transitions from one
quasi-steady state temperature to another.
So what can be done about reducing ticking sounds? Fortunately, there are
several tactics that, when used collectively, will virtually guarantee you
won’t build a radiant panel that sounds like a commercial for Rice Krispies.
Some deal with material choices, while others rely on specific installation
details. Next month we’ll look at ways to put them all together to deliver
silent comfort from plate-based radiant panel systems.
|