Full Circle
by John Siegenthaler, P.E.
May 1, 2008
Will low head loss boilers make a come back?
Some
of you have probably been installing hydronic heating for 30 years or more.
Consider yourselves lucky to have witnessed not only a rebirth of the industry
in North America, but also a steady refinement of technology.
I think it’s safe to say that no one who falls into this vintage is currently
installing systems the same as they did 30 years ago. During the last three
decades, there's been a deluge of new hardware for almost every aspect of the
system from which to choose. Design concepts and objectives have also changed
over this time.
The changes we’ve made and continue to make in system design are influenced by
complex interactions — the people and companies we know, favorite technical
concepts, cost-saving opportunities, energy-saving opportunities, what we read
in trade magazines, and what we observe others doing. This holds true at all
levels of the industry, from installer right up through the manufacturer.
Thinking that we’ll someday arrive at the ultimate design concept and hardware
configuration implies limits that few of us would be willing to accept.
Although what you might be doing today is “state-of-the-art,” it will surely
loose that title, perhaps even by next year.
Without this continuous movement, our industry would eventually cease to exist,
especially as competing technologies constantly offer up a challenge. If you
don’t believe this, do some research on the state of hydronic radiant panel
heating in North America a mere 30 years ago. If PEX tubing hadn’t shown up to
breathe new life into the concept, it was all but dead.
Sometimes our industry goes down technological paths that later prove less than
optimal. Of course, no one realizes this until looking back. Sometimes we also
find that old concepts aren’t necessarily dead, even though they’ve been
mothballed for a while as other “contemporary” approaches enjoy their time in
the spotlight.
This month I want to look at a situation in which a technical detail our
industry relied on extensively 30 years ago, one that some might consider “over
the hill” as evidenced by today’s standard practice, has the potential to
re-emerge and move the industry forward in the process.
A state-of-the-art hydronic heating system circa 1978 was usually built around
a cast-iron or steel boiler connected to a masonry chimney. A site-built black
iron header came off the top or side of that boiler. The tees it contained ran
off to two, or maybe in a big house, three zones of series-connected
finned-tube baseboard. Those zones returned to a corresponding number of zone
valves mounted on the return header. The header connected to a three-piece
circulator, and then to the boiler’s return connection. On the side or front of
the boiler was a tankless coil for domestic water heating.
One of the nice features of this system — though not fully appreciated at the
time — was the low-flow resistance of the boiler and header piping. This
characteristic allowed multiple zones to operate essentially as if they were
stand-alone circuits. When a given circuit turned on or off, there was minimal
affect on other circuits. Things were pretty simple.
Smaller Body, Bigger Head
The
push for increased energy efficiency brought with it some radical new ideas
about boiler design. A trend developed toward low-mass condensing boilers with
heat exchangers made of finned copper tubing or stainless
steel.
This combination certainly reduced the size and weight of boilers, as well as
their warm-up time. In most cases, it also introduced a very different flow
characteristic to the boiler, that of high head loss relative to traditional
boilers.
One early example was the GlowCore boiler, which had a coiled copper heat
exchanger surrounding a cylindrical burner. The pressure drop of the tightly
coiled heat exchanger was much greater than that of other boilers being
installed at the time.
Many installers overlooked the consequences of this characteristic and
installed the GlowCore boiler just like a cast-iron boiler, with all system
flow piped through the boiler. This often bottlenecked the system, leading to
inadequate heat delivery. The opposite situation also occurred when zone valves
were used. Flow starvation through the boiler’s low-mass heat exchanger under
low load conditions lead to damaged heat exchangers.
Some of you probably remember the reputation that GlowCore boilers eventually
got. A reputation that in hind site was largely the result of improper
application and failure to recognize that the industry had reached the point
where not all boilers could be piped the same.
Eventually the industry learned to connect compact condensing boilers into the
system as a secondary circuit with its own dedicated circulator. Today this is
a common detail in installation schematics for such boilers. This realization
even led to the development and use of new devices such as hydraulic
separators.
Are We There Yet?
Adding
a separate circulator, in some cases a high head circulator, solves the issue
of providing adequate boiler flow regardless of what’s happening in the
distribution system. At the same time, it also adds to both installation and
operating cost relative to the older systems, where all flow passed through the
boiler.
In some cases, the hydraulic separation of a boiler from the distribution
system also creates a deviation between boiler outlet temperature and the
temperature of water supplied to the distribution system as shown in Figure 1.
Some boiler operating controls use an externally mounted sensor to measure the
temperature of water supplied to the distribution system; others do not. Those
that don’t are often set to produce an outlet temperature slightly higher than
that needed by the distribution system. This is done in an attempt to keep
supply temperature close to what’s needed after the flows have mixed at the
point of hydraulic separation. This also means the boiler operates at a
temperature higher than necessary and thus at a slightly reduced efficiency.
There are only two ways that I’m aware of to ensure that boiler modulation is
controlled based on the supply temperature to the distribution
system:
Measure this temperature and modulate the burner based on it (e.g.,
using a system supply temperature sensor mounted downstream of the point of
hydraulic separation).
Pass all system flow through boiler and eliminate the hydraulic
separation point and its associated mixing.
Either of these approaches is viable, but the option of passing all flow
through the mod/con boiler offers the added benefit of eliminating the boiler
circulator, its associated piping, and the life-cycle operating cost of this
circulator.
One might argue that the electrical energy consumption associated with pushing
flow through a boiler will occur regardless of whether that power is fed into a
separate boiler circulator or through the system circulator. This is not
necessarily true.
Although the mechanical power to push flow through the boiler at a given flow
rate and associated pressure drop is the same, the corresponding electrical
power required depends on the wire-to-water efficiency of the circulator
supplying the mechanical power. The higher this efficiency, the lower the
electrical power requirement. Thus, if the system circulator can operate at a
higher wire-to-water efficiency than that of a small wet-rotor boiler
circulator, it provides a slight advantage.
This scenario is poised to become more common as ECM-based circulators, with
wire-to-water efficiencies about double those of current PSC-based wet-rotor
circulators, are increasingly used in hydronic distribution systems.
Here’s an example of the potential savings for a small residential
system:
Assume a boiler has a head loss of 4 feet (pressure drop = 1.708 psi) at a
corresponding flow rate of 20 gpm. The estimated electrical power to provide
this condition using a small wet-rotor circulator with PSC motor and 22 percent
wire-to-water efficiency is:
If
this same mechanical energy were supplied from an ECM-based distribution circulator
operating at 40 percent wire-to-water efficiency, the electrical wattage drops
to:
Assuming the boiler operates 3,000 hours per year and
that electricity costs 10 cents per kwhr, the first-year savings would be as
follows (based on the difference in operating wattage):
Over
20 years, with electricity inflating at 4 percent per year, this works out to a
savings of:
Keep in mind that this is in addition to the cost
savings from not installing a separate boiler circulator and associated piping.
This would easily add up to $400 or more in additional savings in a small
residential system.
There are some mod/con boilers available in North America capable of “pump through” application. The
key is minimizing head loss through the boiler.
Although there is no threshold that determines a go/no go decision for pumping
through application, I suggest that the boiler should develop a loss no greater
than 4 feet of head while passing full design flow rate through its heat
exchanger. It’s also beneficial if the boiler’s heat exchanger can operate with
a temperature rise of perhaps 30 degrees F or more under design load. Higher
delta T means lower flow rates, lower head loss and, for a given supply
temperature, lower return temperatures. The latter enhances flue gas condensation
and boosts efficiency.
Will the future of mod/con boilers be “pump through” design? Will we eventually come back to systems as
simple as a single-system pump (ECM-based variable speed) pushing flow through
the boiler and then on to a distribution system zoned using zone valves or
TRVs? Such an approach surely offers simplicity. It also reduces both
installation and operating cost, as well as eliminates temperature variation
between the boiler outlet and system supply. These characteristics are
beneficial to both the customer and the installer.
|