Not from the boiler, but from the point of no
pressure change.
The What
The objective in a hydronic circuit is to
increase the pressure within most of the circuit when the circulator is
operating. This produces several benefits, including:
- It “moves” water farther from its flash point. In other words,
increasing the pressure on water helps suppress boiling. This is especially
important in preventing vaporous cavitation at the eye of the circulator’s
impeller. It can also suppress cavitation in throttling
valves.
- Molecules of dissolved gases are encouraged to stay in solution, thus
ensuring quiet operation of the circulator.
- It helps eject any air that has accumulated in air
vents.
- Air is prevented from being “sucked” into the piping circuit at
points that might be drawn to subatmospheric pressure when the circulator
operates, due to incorrect design.
An operating circulator adds head energy to the fluid passing through it. The
“evidence” of the added head is pressure differential across the circulator.
The outlet pressure is always higher than the inlet pressure.
To increase the pressure in most of the circuit requires that the differential
pressure created by the circulator be added to, rather than subtracted from,
the static pressure in the system. To make this happen, the circulator needs to
“pump away” from the point of no pressure change (PONPC) in the circuit.
In a simple-series hydronic circuit, the PONPC will always be where the
expansion tank connects to the circuit. It follows that the circulator should “pump
away” from this point. This is accomplished in the system shown in Figure
1.
This layout is quite popular in North America.
The expansion tank threads into the bottom of the air separator. There’s very
little pressure drop between the PONPC and the boiler. If the boiler has low
head loss characteristics, there also will be very little pressure drop across
it as the circulator operates. The pressure relief valve mounted to the boiler
experiences very little change in pressure when the circulator turns on. This
is good.
I recommend at least 10 pipe diameters of
straight pipe upstream of the circulator’s inlet flange. This is another “standard
detail” that reduces turbulence into the circulator and keeps things
quiet.
The configuration shown in Figure 2 is less used but just as valid from the
standpoint of hydraulics. Although the expansion tank has moved several feet
away from the circulator’s inlet, the pressure drop represented by the piping
path between the circulator and expansion tank is still very low relative to
the pressure drop around the remainder of the distribution circuit. This allows
most of the pressure differential created by the circulator to raise the
pressure in the distribution circuit.
This approach also keeps the expansion tank on
the “cool” side of the heat source. Reduced heating of the expansion tank shell
reduces both static pressure increases and extraneous heat loss from the
system. It’s also likely that tanks operating at lower temperatures will have
longer diaphragm life.
Avoid the system shown in Figure 3. This design allows the pressure
differential created by the circulator to add to the pressure in the boiler.
Although the boiler is probably more than capable of handling the increased pressure,
the pressure relief valve piped to the boiler also feels the pressure increase.
Depending on the static pressure in the system, it’s possible the relief valve
could start dribbling or open when the circulator turns on.
When It’s Not A Simple Loop
In a primary/secondary piping system, the
secondary circuits “see” the primary loop as their expansion tank. The closely
spaced tees that couple the secondary circuit to the primary loop become the
PONPC for the secondary circuits. Thus, install circulators so they push water
into the secondary circuit as shown in Figure 4.
In systems with a hydraulic separator, the expansion tank can be placed almost
anywhere in the vicinity of the hydraulic separator. I typically show it near
one of the lower connections (e.g., system return or boiler return). Some
hydraulic separators even have a tapping or extension near the bottom to which
the expansion tank can connect. Although fine from a hydraulics standpoint, I
urge you to install the tank so that sediment that may accumulate at the bottom
of the hydraulic separator will not drop down onto the top of the expansion
tank’s diaphragm. Use a tee and some elbows to offset the expansion tank as
shown in Figure 5.
Pumping away means away from the point of no pressure change rather than away
from the boiler. Use it on every installation and enjoy the benefits.