Releasing Solar Heat
by John Siegenthaler, P.E.
December 20, 2009
Which hydronic heat emitters work bestwith solar
thermal systems?
In past Solar Heating
Report articles, we’ve discussed systems for capturing solar
energy for domestic water heating and space heating. The “golden rule” in
designing such systems is to keep the operating temperature of the collectors
as low as possible. This is true for both evacuated tube and flat-plate
collectors, although the latter is especially sensitive to increases in entering
fluid temperature.
With respect to space heating, the operating temperature of the collector array
is largely determined by the distribution system the solar subsystem connects
to.
Traditional hydronic heat emitters such as fin-tube baseboard are usually sized
to the relatively high water temperatures available from conventional boilers —
160- to 200-degree F supply water at design load conditions. Expecting any
solar collector array to efficiently and consistently produce such temperatures
in the dead of winter is unrealistic.
One might argue that using additional baseboard would bring the required supply
water temperature down. This is true. The graph in Figure 1 shows the output of
typical residential fin-tube baseboard over a range of water
temperatures.
The output of fin-tube baseboard at an average water temperature of 120 degrees
F is about
160 Btu/hr./ft. of finned element. That’s about 33 percent of its output when
operating with an average water temperature of 180 degrees F. The implication
is that more than three times the baseboard would be required in the building
if the supply water temperature under design load was limited to 120 degrees F.
Few buildings have the wall space for this much baseboard; even fewer owners
would find this amount of baseboard aesthetically acceptable. Clearly baseboard
is not well-suited for use in solar combisystems.
Is Floor Heating The Answer?
Many of those who have used slab-type floor heating
may wonder why this question is even asked. After all, slab-type floor heating,
with low-resistance finish flooring, has one of the lowest water temperature
requirements of any hydronic heat emitter. The graph of Figure 2 indicates that
a bare slab with 12-inch tube spacing can emit 20 Btu/hr./ft.2 when
the average water temperature in the circuit(s) is 22.5 degrees above room
temperature. For a room maintained at 70 degrees F, this means an average
circuit water temperature of 92.5 degrees F could maintain this
output.
The supply water temperature would likely be 5 to 8 degrees higher (97.5 to
100.5 degrees F). Tightening tube spacing to 6 inches reduces these
temperatures about 5 degrees, an even more favorable situation for the solar
collectors. So why wouldn’t heated floor slabs always be the obvious choice for
use with solar combisystems?
The answer lies in the building itself. If it is well-insulated and designed
for passive solar gain, the building’s thermal characteristics can conflict
with the time-delayed response of heated floor slabs.
Consider the following situation. An eco-friendly home is being constructed
with southerly exposed windows totaling 8 to 10 percent of its floor area.
These windows will flood a beautifully stained and sealed concrete floor slab with
solar energy during sunny winter days. The slab will readily absorb this energy
and store it for release after the sun has set and on into the night. This is
classic “direct-gain” solar architecture.
Wanting to take advantage of generous state and
federal tax incentives, the owner also decides to include a solar combisystem
in the building project. He reasons that the warm water it generates can
circulate through PEX tubing embedded in the floor slab during early morning
hours after the passive energy gains have dissipated, as well as during times
of low solar gain. An auxiliary boiler is included to ensure the floor doesn’t
cool off waiting for the sun to return.
Now imagine a cold winter night when the embedded tubing and boiler are doing
their thing to keep the floor toasty. By 7 the next morning, it’s 0 degrees F
outside and the floor surface temperature is a barefoot-friendly 83 degrees F.
No problems so far.
The sun rises on this clear and cold morning, and by 9 a.m. there’s significant
solar energy shining through those windows. The thermostat has stopped flow
through the floor circuits since the indoor air temperature is now about 73
degrees F. However, just because flow through the floor has stopped doesn’t
mean that heat output from the floor also stops. The floor surface is still
about 10 degrees warmer than room air and most of the interior room surfaces.
The floor continues to release heat even as the room temperature climbs to 80
degrees F.
By early afternoon, the interior room temperature reaches 87 degrees F. The
owner has stripped down to a T-shirt and opened windows to prevent any further
rise in interior temperature.
This all happened because the floor slab was already “charged” with heat when
the sun came out in the morning. As such, it was incapable of absorbing
additional heat from solar gains and the building quickly overheated. The net
effect was that much of the direct solar gain was lost through ventilation to
prevent the building from turning into an even warmer sauna.
So What’s The Answer?
-fig-4_sm.jpg) |
| Figure 4: A heated stair banister can provide warmth
inconspicuously. |
|
The ideal hydronic heat emitter for the scenario
described above would operate on low water temperatures and have very low
thermal mass.
One possibility is a low-mass radiant wall constructed as shown in Figure
3.
The majority of this panel’s thermal mass is the 1/2-inch-thick drywall, which,
on a square footage basis, has about 9 percent of the thermal mass of a
4-inch-thick concrete slab. Low mass means faster response.
Site-built radiant walls can be inconspicuously integrated into building
surfaces, such as the heated stair banister wall shown in Figure
4.
Another excellent solution is low-mass panel radiators such as those shown in
Figure 5.
Most panel radiators have low water volume relative to their rated output. This
characteristic, in combination with low metal weight, makes them fast
responders when turning on and, even more importantly, when turning
off.
For example, a typical fluted-steel panel radiator 24 inches high by 72 inches
long by 4 inches thick contains about 2.1 gallons of water and has an empty
weight of about 127 pounds. Its total thermal mass is equivalent to 3.4 square
feet of 4-inch-thick concrete slab.
Panel radiators can be sized for relatively low operating water temperatures.
For good solar collector efficiency, I suggest nothing higher than 120-degree F
average water temperature under design load conditions.
-fig-5.jpg) |
| Figure 5: Panel radiators offer an excellent solution to provide
warmth in these systems. (Photo credits: Myson (left) and Runtal (right). |
|
As was the case with fin-tube baseboard, size has to
be significantly increased to adjust for lower operating temperature. A typical
fluted-steel panel radiator operating at an average water temperature of 120
degrees F in a 70-degree F room releases about 30 percent as much heat as it
would operating at an average water temperature of 180 degrees
F.
A 200-square-foot room in a building with a design heat loss of 20 Btu/hr./ft.2
would need a panel capable of releasing 4,000 Btu/hr. A panel radiator 24
inches square by 4 inches thick could supply this output if operated at an
average water temperature of 180 degrees F. However, a radiator 24 inches high
by 72 inches long by 4 inches thick would be required to meet this load if
operated at an average water temperature of 113 degrees F.
Under partial load conditions, the supply water temperature would be reduced
using outdoor reset control. At an outdoor temperature of 30 degrees F, the
24-inch by 72-inch by 4-inch
panel described would only require an average water temperature of about 95
degrees F. The lower the system’s operating temperature, the higher the
efficiency of its solar collectors.
Hydronics technology is the “glue” that holds solar combisystems together.
Contemporary hydronic heat emitters such as low-mass radiant walls and panel radiators,
although not designed exclusively for solar combisystems, are nonetheless
excellent performers in such applications.
|