Don’t Shorten An Electric Floor Heating Roll
 |
| Scott Rosenbaum |
|
On most jobsites, things are never what you expect and
measurements frequently change. If you come to the jobsite and notice your
electric floor heating roll is now too long, don’t shorten it. Call your
manufacturer for an exchange.
If a roll is shortened, it will increase
the watts per square foot above a level allowed by the NEC (15 watts per square
foot). You can shorten the cold lead wires used to connect the roll to the thermostat,
but you cannot shorten the heating cable that is sewn to the fiberglass mesh.
To avoid these issues, I recommend you
get a custom installation plan with all your projects involving fixtures, such
as kitchen or bath cabinets. Several manufacturers offer installation plans as
a free service. Take advantage of this. This will help you identify job changes
and adapt quickly. You don’t want to start laying out your electric floor
heating roll only to find out at the end that you have three extra feet.
Forgot To Test Beforehand And Now There’s A Problem?
If there is a problem with the heated floor, the system
should be tested. A digital volt/ohms meter is necessary to verify that the
thermostat has the correct voltage available.
First try resetting the circuit breaker.
If the thermostat is getting the correct power, it should be tested to see if
the power is being passed by the thermostat into the floor. When the wavy lines
are showing in the thermostat display window, the thermostat should be passing
line voltage to the floor. If it doesn’t, the thermostat is malfunctioning or
is not wired correctly to the floor leads.
If the thermostat is functioning
correctly, the floor rolls need to be tested.
- Disconnect the
wires from the thermostat.
- Set the ohms meter to
the 200 range.
- Attach one center core wire to each
meter probe. The ohms reading should correspond with the numbers that appear on
the label affixed to the roll. If the ohms reading is not within the +/- 15 percent
margin, the roll may be defective.
- If the readings
match the spec, attach a braided sheath from each end of the wire to each
probe. This reading should be within 15 percent of the spec on the roll’s
label; if not, the roll may be damaged.
The final two tests of the
roll are to test each wire end separately.
- Attach one meter
probe to the center core of one wire.
- Attach the
other probe to the braided sheath of the same wire end. This ohm reading should
be OL or INF.
- Now test the other wire end. This
reading should be the same. This reveals that there is no short between the
inner core conductor and the braided sheath that surrounds it. If there is an
ohm reading on either end, the roll has a short.
If there are no
ohms readings on the core or ground sheaths, the wire has been severed.
- A
“shortstop”* can be used to find the break. This device sends a signal down one
end of the wire and measures the distance to the short or break. Once this
number is obtained, the device is attached to the other end of the wire and the
test repeated.
- The numbers obtained from these tests
will indicate the approximate position of the damaged area in the room, if the
installation plan was used. This device will not work if the roll is laid
without a plan or the plan was changed.
It is surprising how many problems we see in Tech Support
that can be easily avoided. By following these simple steps, tips and tests,
your installations should be problem-free.
* Contact the manufacturer for
circuit checks and shortstops.